5 Install Rack Options 37
Connect CAT5e Wiring
Step 1: Pull your CAT5e building wire through the conduit access previously prepared.
Step 2: The punch down connector provides insulation displacement therefore stripping
of wire is not required. Reference the connector label for the color code for Cat5e
wire using the 568B standard.
Step 3: Install the protective covers over the wire terminals.
Step 4: Install the punch down connector on the patch panel.
Step 5: Connect Ethernet patch cables.
a: Connect a patch cable from the left I/O to the first RJ-45 input on the Ethernet
Switch panel.
b: Connect a patch cable from the punch down connector to an RJ-45 input on
the switch panel. Repeat for each building service connection (up to four).
Step 6: Install the Ethernet Switch Module into the enclosure and secure it in place using
the captured screws provided.
Note:
All Ethernet terminations must follow IEEE 802.3 and be terminated to the T568B
standard.
Note:
Use a 110 punch down tool to complete the wire termination.
As needed, press here gently
with screwdriver to release
connector from panel.